ALARMSbox
TheALARMindicatorwillbegreyifnoalarmconditionexists.Itwillflashbetweenyellowandredifanalarm
conditionexists.Themenuprovidesforadjustingalarmsettings.
TheALARMSTATUStextboxwillindicatethenatureofthealarmifanalarmconditionsexists.
NOLATCHES:if
analarmconditionclearsitself,thealarmwillautomaticallyreset.
ALARM1LATCH:ifanalarmistriggeredfromthecontrolsensor,thesoftwarewillcontinuetosignalanalarm
conditionuntiltheconditionisclearedandtheALARMLACTHCLEARbuttonisclicked.
ALARM2LATCH:ifan
alarmistriggeredfromthesecondarysensor,thesoftwarewillcontinuetosignalanalarm
conditionuntiltheconditionisclearedandtheALARMLACTHCLEARbuttonisclicked.
ALARM1&2LATCH:ifanalarmistriggeredfromeitherthecontrolorthesecondarysensor,thesoftwarewill
continueto
signalanalarmconditionuntiltheconditionisclearedandtheALARMLACTHCLEARbuttonisclicked.
ALARM1HIGHSETTING:thissetsthetemperatureatwhichanalarmwilloccurifthecontrolsensortemperature
exceedsthesetvalue.Thesetvaluemustbegreaterthanthevalueset
intheALARM1LOWSETTINGbutlessthan
200.Ifthesetvalueissettogreaterthan199,noalarmwillbesignaledforanyovertemperaturecondition.
ALARM1LOWSETTING:thissetsthetemperatureatwhichanalarmwilloccurifthecontrolsensortemperature
becomes
lessthanthesetvalue.ThesetvaluemustbelessthantheALARM1HIGHSETTINGbutgreaterthan‐21.
Ifthesetvalueislessthan‐20,noalarmwillbesignaledforanyundertemperaturecondition.
ALARM1DEADBAND:thisdefinesatemperaturedifferenceaboveorbelow
theALARM1LOWSETTINGorALARM
1HIGHSETTINGatwhichthealarmstatuscanbecleared(eitherautomaticallyormanuallydependingonlatch
settings).Forexample,ifALARM1HIGHSETTINGissetfor70andtheALARM1DEADBANDissetfor10,andan
alarmconditionoccurs,
thecontrolsensorwouldhavetocoolto60°Cbeforethealarmcanbereset.